Laser equipment
| Model Number:-- | Place of Origin:Shenzhen,China |
| Price:-- | Packing:Plywood case |
| Transport mode:by sea or by air | Minimum Order:1 set |
Online Postings: Products (54), offers (51)
Country/Territory: China
Business Type: Manufacture
Number of Employees: 51 ~ 200 People
|
Model Item |
AL-3W |
AL-5W |
AL-6W |
AL-8W(D) |
AL-10W(D) | ||||||
|
nominal cooling capacity |
kcal/h |
6803 |
11094 |
13089 |
17604 |
22188 | |||||
|
kw |
7.91 |
12.9 |
15.22 |
20.47 |
25.8 | ||||||
|
input power |
kw |
3.33 |
5.8 |
6.33 |
9.25 |
10.37 | |||||
|
power supply |
3PH ~ 380V 50HZ | ||||||||||
|
refrigerant |
type |
R22 | |||||||||
|
type of control |
capillary | ||||||||||
|
compressor |
type |
hermetic scroll (piston) | |||||||||
|
power(kw) |
2.8 |
4.66 |
5.2 |
3.8×2 |
4.66×2 | ||||||
|
condenser |
type |
finned copper tube + low noise outer rotor fan | |||||||||
|
cooling air flow (m 3 /h) |
3000 |
5000 |
6000 |
8000 |
10000 | ||||||
|
evaporator |
type |
water tank with coil | |||||||||
|
chilled fluid flow(m 3 /h) |
1.36 |
2.22 |
2.6 |
3.52 |
4.44 | ||||||
|
volume(L) |
50 |
70 |
70 |
120 |
200 | ||||||
|
inlet and outlet pipe diameter (inch) |
1 |
1 |
1 |
1 |
1-1/2 | ||||||
|
drain |
1/2 | ||||||||||
|
pump |
power (kw) |
0.55 |
0.55 |
0.55 |
0.75 |
0.75 | |||||
|
lift(m) |
22 |
22 |
22 |
25 |
25 | ||||||
|
flow switch |
| ||||||||||
|
safety protection |
compressor over temperature, over current, high and low pressure, over temperature,flow Switch, phase sequence, phase-missing, exhaust overheating, antifreezing | ||||||||||
|
weight |
kg |
135 |
175 |
180 |
310 |
450 | |||||
|
dimension |
mm |
930*520*970 |
1140*560*1040 |
1140*560*1040 |
1310*720*1270 |
1680*810*1280 | |||||
|
Note: 1. nominal cooling capacity is according to: Inlet chilled fluid temperature: 12 Outlet chilled fluid temperature: 7 Inlet cooling air temperature: 30 Outlet cooling air temperature: 35 2. working range: The temperature range of chilled fluid is from 5 to 35; Temperature difference between inlet and outlet chilled fluid is from 3 to 8. The machine should be used when the ambient temperature at or below 35. We reserve the right to modify the above dimensions or parameters without further notice. | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|