group nameVT Text & Graphic
Min Order1 piece
brand nameVICPAS
modelVT1001SE000
payment methodWestern Union, T/T, PayPal, T/T ,Credit Card, Western Union
update timeFri, 08 Nov 2024 12:13:45 GMT
Brand ESA
Warranty 180 Days
Product Line VT Text
Supply VT100 Membrane Keypad
Min Order1 piece
ESA VT100 can be supplemented with accessories to boost and broaden theirperformance.
ESA VIDEO TERMINAL (VT) is a device that allows the user to control orsimply monitor a productive process. It can send commands using configuredby the user; it can send data determining the process on hand andcan display information deriving from the productive process. The informationcan be in the form of an Alarm, an Information (Info-) Message or inbinary data format.
The VTs can be divided into two groups: those with a keyboard and thosewithout but equipped with a Touch Screen.
VICPAS supply ESA TEXT HMI VT100 membrane switch with 6 months warranty and support Urgent Worldwide Shipping.
The table below describes the parameters of the ESA VT1001SE000 HMI Parts.
Brand: | ESA |
Numerical keypad: | NO |
Input fuse: | Internal DC fuse |
Warranty: | 6-Months Warranty |
Product Line: | VT TEXT |
Display Type: | TEXT LCD |
Columns by rows: | 20 * 4 |
Display area size: | 70.4 * 20.8 |
Input voltage: | 18 - 32 V DC |
Part Number: | VT1001SE000 |
Related ESA VT100 Part No. :
ESA VT100 | Description | Inventory status |
VT1001SP000 | ESA Text HMI VT100 VT1001SP000 Membrane Keypad Replacement | In Stock |
VT1001SF000 | ESA Text HMI VT100 VT1001SF000 Membrane Switch Replacement | In Stock |
VT1001SE000 | ESA Text HMI VT100 VT1001SE000 Membrane Keyboard | In Stock |
ESA VT TEXT | Description | Inventory status |
Question: How to adjust the contrast on the ESA VT100 Display?
Answer:To improve the quality of the representation on the display it may be necessaryto adjust its contrast. This can be done by rotating the trimmer (C) atthe back of the VT ; turn it (using a small screwdriveror a trimmer tool) in one direction and, if the display quality worsens,turn it the other way.
Question: What is the VT100 Termination of CAN line?
Answer:The VT in question integratesthe termination resistances of the serial line (typically 120 ohms)which can be inserted by means of a jumper (preset on 1-2, line not terminated).To activate the termination:
• Make sure the device is not connected to the power supply.
• Remove the cover.
• Identify the jumper unit J2.
• Position the jumper between pins 2 and 3 (line terminated).
• Replace the back cover.
• Reconnect the power supply.
Question: What is ESA VT100 mebrane keyboard HMI parts price?
Answer: Submit a fast quote, send VICPAS an email for best price.
网络文化经营许可证:浙ICP备14006100号-11 2007-2024 Tradevv.com. All rights reserved.