ESA VT100 can be supplemented with accessories to boost and broaden their performance.
ESA VIDEO TERMINAL (VT) is a device that allows the user to control or simply monitor a productive process. It can send commands using configured by the user; it can send data determining the process on hand and can display information deriving from the productive process. The information can be in the form of an Alarm, an Information (Info-) Message or in binary data format.
The VTs can be divided into two groups: those with a keyboard and those without but equipped with a Touch Screen.
VICPAS supply ESA TEXT HMI VT100 membrane switch with 6 months warranty and support Urgent Worldwide Shipping.
The table below describes the parameters of the ESA VT1001SP000 HMI Parts.
Brand: | ESA |
Numerical keypad: | NO |
Input fuse: | Internal DC fuse |
Warranty: | 6-Months Warranty |
Product Line: | VT TEXT |
Display Type: | TEXT LCD |
Columns by rows: | 20 * 4 |
Display area size: | 70.4 * 20.8 |
Input voltage: | 18 - 32 V DC |
Part Number: | VT1001SP000 |
Related ESA VT100 Part No. :
ESA VT100 | Description | Inventory status |
VT1001SP000 | ESA Text HMI VT100 VT1001SP000 Membrane Keypad Replacement | In Stock |
VT1001SF000 | ESA Text HMI VT100 VT1001SF000 Membrane Switch Replacement | In Stock |
VT1001SE000 | ESA Text HMI VT100 VT1001SE000 Membrane Keyboard | In Stock |
ESA VT TEXT | Description | Inventory status |
Question: How to adjust the contrast on the ESA VT100 Display?
Answer:To improve the quality of the representation on the display it may be necessaryto adjust its contrast. This can be done by rotating the trimmer (C) atthe back of the VT ; turn it (using a small screwdriveror a trimmer tool) in one direction and, if the display quality worsens,turn it the other way.
Question: What is the VT100 Termination of CAN line?
Answer:The VT in question integratesthe termination resistances of the serial line (typically 120 ohms)which can be inserted by means of a jumper (preset on 1-2, line not terminated).To activate the termination:
• Make sure the device is not connected to the power supply.
• Remove the cover.
• Identify the jumper unit J2.
• Position the jumper between pins 2 and 3 (line terminated).
• Replace the back cover.
• Reconnect the power supply.